Back to Top

1
Hi, Guest!
  • SCHNEIDER ELECTRIC
  • 59704 Environ base unit SEP383 for Sepam series 80 - 24…250 V - with a

59704 Environ Base Unit SEP383 For Sepam Series 80 - 24…250 V - With A

Update Terakhir
:
03 / 10 / 2023
Min. Pembelian
:
1 Unit

Harga

CALL
PT. SURYA HAWILA PERKASA , founded in 2006 has been growing up to a leading one-stop soluton provider for intelligent electrical distribution and energy efficiency systems.

We gives the best solutions for Industrial Automation products and services, Electrical, consultant, training.

Detail 59704 Environ Base Unit SEP383 For Sepam Series 80 - 24…250 V - With A

Protection Relay

base unit SEP383 for Sepam series 80 - 24…250 V - with advanced UMI

Specifications

Main
Range of product : Sepam series 80
Device short name : SEP383
User machine interface type : Advanced

Complementary
UMI indication :
- Status of logic inputs
- Logipam data
- Metering and diagnosis data
- Main protection settings
- Version of Sepam and remote modules
- List of activated protection functions
- Alarms and operating messages
UMI control :
- Alarm acknowledgement
- Output testing
- Sepam reset
Display resolution : 128 x 64 pixels
Number of key : 9
Local signalling :
- 2 LEDs for Sepam operating status (back part)
- 2 LEDs for Sepam operating status (front face)
- 9 LEDs for indication of parameters (front face)
Output type :
- Annunciation relay: 100...240 V AC 47.5...63 Hz continuous current: 2 A breaking capacity: 1 A cos φ > 0.3
- Annunciation relay: 127 V DC continuous current: 2 A breaking capacity: 0.5 A L/R < 20 ms
- Annunciation relay: 220 V DC continuous current: 2 A breaking capacity: 0.15 A L/R < 20 ms
- Annunciation relay: 24 V DC continuous current: 2 A breaking capacity: 2 A L/R < 20 ms
- Annunciation relay: 48 V DC continuous current: 2 A breaking capacity: 1 A L/R < 20 ms
- Control relay: 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity: 5 A cos φ > 0.3 making capacity: < 15 A for 200 ms
- Control relay: 100...240 V AC 47.5...63 Hz continuous current: 8 A breaking capacity: 8 A resistive making capacity: < 15 A for 200 ms
- Control relay: 127 V DC continuous current: 8 A breaking capacity: 0.2 A L/R < 40 ms making capacity: < 15 A for 200 ms
- Control relay: 127 V DC continuous current: 8 A breaking capacity: 0.5 A L/R < 20 ms making capacity: < 15 A for 200 ms
- Control relay: 127 V DC continuous current: 8 A breaking capacity: 0.7 A resistive making capacity: < 15 A for 200 ms
- Control relay: 220 V DC continuous current: 8 A breaking capacity: 0.1 A L/R < 40 ms making capacity: < 15 A for 200 ms
- Control relay: 220 V DC continuous current: 8 A breaking capacity: 0.2 A L/R < 20 ms making capacity: < 15 A for 200 ms
- Control relay: 220 V DC continuous current: 8 A breaking capacity: 0.3 A resistive making capacity: < 15 A for 200 ms
- Control relay: 24 V DC continuous current: 8 A breaking capacity: 4 A L/R < 40 ms making capacity: < 15 A for 200 ms
- Control relay: 24 V DC continuous current: 8 A breaking capacity: 6 A L/R < 20 ms making capacity: < 15 A for 200 ms
- Control relay: 24 V DC continuous current: 8 A breaking capacity: 8 A resistive making capacity: < 15 A for 200 ms
- Control relay: 48 V DC continuous current: 8 A breaking capacity: 1 A L/R < 40 ms making capacity: < 15 A for 200 ms
- Control relay: 48 V DC continuous current: 8 A breaking capacity: 2 A L/R < 20 ms making capacity: < 15 A for 200 ms
- Control relay: 48 V DC continuous current: 8 A breaking capacity: 4 A resistive making capacity: < 15 A for 200 ms
[Us] rated supply voltage : 24/250 V DC tolerance: - 20...10 % maximum consumption: < 16 W
Supply inrush current : < 10 A for 10 ms at 24/250 V DC
Battery type : Lithium 3.6 V size: 1/2 AA
Battery life :
- 10 year(s) (Sepam energized)
- 8 year(s) (Sepam not energized)
Mounting mode : Fixed
Mounting support : Plate
Height : 222 mm
Width : 264 mm
Depth : 89.7 mm
Net weight : 3.62 kg
Power frequency dielectric withstand :
- 2 kV during 1 min conforming to IEC 60255-5
- 1 kV (indication output) during 1 min conforming to ANSI C37.90
- 1.5 kV (control output) during 1 min conforming to ANSI C37.90
[Uimp] rated impulse withstand voltage : 5 kV (1.2/50 µs) conforming to IEC 60255-5
Mechanical robustness :
- Earthquakes in operation (level: 2) : 1 Gn (vertical axes) conforming to IEC 60255-21-3
- Earthquakes in operation (level: 2) : 2 Gn (horizontal axes) conforming to IEC 60255-21-3
- Jolts de-energized (level: 2) : 20 Gn/16 ms conforming to IEC 60255-21-2
- Shocks de-energized (level: 2) : 27 Gn/11 ms conforming to IEC 60255-21-2
- Shocks in operation (level: 2) : 10 Gn/11 ms conforming to IEC 60255-21-2
- Vibrations de-energized (level: 2) : 2 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
- Vibrations in operation (level: 2) : 1 Gn, 10 Hz...150 Hz conforming to IEC 60255-21-1
- Vibrations in operation (level: Fc) : 2 Hz...13.2 Hz, a = +/- 1 mm conforming to IEC 60068-2-6

Environment
Standards :
- CSA C22.2 No 14-95
- CSA C22.2 No 94-M91
- EN 50263
- CSA C22.2 No 0.17-00
- UL 508
Product certifications :
- UL 508 file N° 212533
- CE
- C22.2 file N° 210625
Fire resistance : 650 °C conforming to IEC 60695-2-11
IP degree of protection :
- Other panels: IP20 conforming to IEC 60529
- Front panel: IP52 conforming to IEC 60529
NEMA degree of protection : Type 12 conforming to NEMA
Immunity to microbreaks : 100 ms
Electromagnetic compatibility :
- Fast transient bursts: (immunity tests-conducted disturbances), A and B, 4kV, 2.5 kHz/2 kV, 5 kHz, conforming to IEC 60255-22-4
- Fast transient bursts: (immunity tests-conducted disturbances), IV, 4kV, 2.5 kHz, conforming to IEC 61000-4-4
- Immunity to conducted RF disturbances: (immunity tests-conducted disturbances), III, 10 V, conforming to IEC 60255-22-6
- Immunity to magnetic fields at network frequency: (immunity - - tests-radiated disturbances), IV, 30 A/m (continuous)-300 A/m (13 s), conforming to IEC 61000-4-8
- Immunity to radiated fields: (immunity tests-radiated disturbances), III, 10 V/m, 80 MHz...2 GHz, conforming to IEC 61000-4-3
- Surges: (immunity tests-conducted disturbances), III, 2 kV CM, 1 kV MD, conforming to IEC 61000-4-5
- Conducted disturbance emission: (emission tests), conforming to IEC 60255-25
- Disturbing field emission: (emission tests), conforming to IEC 60255-25
- Disturbing field emission: (emission tests), A, conforming to EN 55022
- Electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 4 kV contact, conforming to ANSI C37.90.3
- Electrostatic discharge: (immunity tests-radiated disturbances), 8 kV air, 6 kV contact, conforming to IEC 60255-22-2
- Fast transient bursts: (immunity tests-conducted disturbances), 4kV, 2.5 kHz, conforming to ANSI C37.90.1
- Immunity to radiated fields: (immunity tests-radiated disturbances), 10 V/m, 80 MHz...1 GHz, conforming to IEC 60255-22-3
- 1 MHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV CM, 1 kV MD, conforming to IEC 60255-22-1
- 1 MHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV CM, 2.5 kV MD, conforming to ANSI C37.90.1
- 100 kHz damped oscillating wave: (immunity tests-conducted disturbances), 2.5 kV CM, 1 kV MD, conforming to IEC 61000-4-12
- Conducted disturbance emission: (emission tests), A, conforming to EN 55022
- Immunity to radiated fields: (immunity tests-radiated disturbances), 35 V/m, 25 MHz...1 GHz, conforming to ANSI C37.90.2
- Voltage interruptions: (immunity tests-conducted disturbances), 100 % during 100 ms, conforming to IEC 60255-11
Climatic withstand :
- Continuous exposure to damp heat (in operation) : Cab: 10 days, 93 % RH, 40 °C conforming to IEC 60068-2-78
- Continuous exposure to damp heat (in storage) : Cab: 56 days, 93 % RH, 40 °C conforming to IEC 60068-2-78
- Continuous exposure to damp heat (in storage) : Db: 6 days, 95 % RH, 55 °C conforming to IEC 60068-2-30
- Exposure to cold (in operation) : Ad: - 25 °C conforming to IEC 60068-2-1
- Exposure to cold (in storage) : Ab: - 25 °C conforming to IEC 60068-2-1
- Exposure to dry heat (in operation) : Bd: 70 °C conforming to IEC 60068-2-2
- Exposure to dry heat (in storage) : Bb: 70 °C conforming to IEC 60068-2-2
- Salt mist (in operation) : Kb/2: 6 days conforming to IEC 60068-2-52
- Temperature variation with specified variation rate (in storage) : Nb: - 25 °C to 70 °C, 5 °C/min conforming to IEC 60068-2-14
- Influence of corrosion/gaz test 2 (in operation) : 21 days, 75 % RH, 25 °C, 0.5 ppm H2S, 1 ppm S02 conforming to IEC 60068-2-60
- Influence of corrosion/gaz test 4 (in operation) : 21 days, 75 % RH, 25 °C, 0.01 ppm H2S, 0.2 ppm S02, 0.2 ppm NO2, 0.01 ppm CI2 conforming to IEC 60068-2-60

Packing Units
Unit Type of Package 1 : PCE
Number of Units in Package 1 : 1
Package 1 Height : 19.000 cm
Package 1 Width : 28.500 cm
Package 1 Length : 36.000 cm
Package 1 Weight : 3.000 kg
Unit Type of Package 2 : S04
Number of Units in Package 2 : 3
Package 2 Height : 30.000 cm
Package 2 Width : 40.000 cm
Package 2 Length : 60.000 cm
Package 2 Weight : 9.727 kg
Unit Type of Package 3 : P12
Number of Units in Package 3 : 12
Package 3 Height : 50.000 cm
Package 3 Width : 80.000 cm
Package 3 Length : 120.000 cm
Package 3 Weight : 51.388 kg
Tampilkan Lebih Banyak
Kontak Kami